Gate valve installation points

Author:Gate valve     Published time:2019-05-15 09:58     Reading times:854    

Gate valve installation points

 

The opening and closing member of the gate valve is a gate. The direction of movement of the gate is perpendicular to the direction of the fluid. The gate valve can only be fully open and fully closed, and cannot be adjusted and throttled. The direction of the gate movement of the gate valve is perpendicular to the direction of the fluid. The gate valve can only be fully open and fully closed, and cannot be adjusted and throttled. The gate has two sealing faces. The two sealing faces of the most common mode gate valves form a wedge shape, and the wedge angle varies with valve parameters.

 

The main points of installation of the Gate valve are as follows:

 

1. The installation position, height, and import and export direction must meet the design requirements, and the connection should be firm and tight.

 

2. All kinds of manual valves installed on the insulated pipe, the handles must not be downward.

 

3. The valve must be inspected before installation. The nameplate of the valve should conform to the current international standards. For valves with working pressure greater than 1.0 MPa and cutting off on the main pipe, the strength and tight performance test should be carried out before installation. use. In the strength test, the test pressure is 1.5 times the nominal pressure, the duration is not less than 5 min, and the valve casing and the packing should be free of leakage. In the rigorous test, the test pressure is 1.1 times of the nominal pressure; the test pressure shall meet the requirements of international standards during the duration of the test, and the leakage of the sealing surface of the ram shall be qualified.

 

Skype
Email
TOP